Destiny 4100 Especificaciones Pagina 31

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 64
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 30
31
System Times And Other Options
System Time Options - A description of each time is available in the Glossary Units Location Default
Entry delay 1 (Not to exceed 45 seconds in a UL installation)
.......................
seconds
....
0080
......
020
_______
Entry delay 2 (Not to exceed 45 seconds in a UL installation)
.......................
seconds
....
0081
......
020
_______
Exit delay (Not to exceed 60 seconds in a UL installation)
............................
seconds
....
0082
......
030
_______
Alarm cut off and reset (Not to be less than 4 minutes in a UL installation)
..
minutes
....
0083
......
005
_______
* Duration between fire, tamper, trouble chirps
...............................................
seconds
....
0086
......
005
_______
* Duration for recognition of AC power loss
.....................................................
minutes
....
0097
......
001
_______
Duration between spoken "Pre-alarm" cycles (000 = 3 seconds)
.....................
seconds
....
0099
......
000
_______
Fire siren tone duration before speech
..............................................................
seconds
....
0101
......
005
_______
Burglary siren tone duration before speech
......................................................
seconds
....
0102
......
005
_______
#Fire cut off and reset
........................................................................................
minutes
....
0100
......
005
_______
Number of 4 second samples to determine loss of phone line
.........................
samples
....
0456
......
006
_______
Time frame for User Test Timeout
.....................................................................
minutes
....
0098
......
003
_______
Smoke verification smoke off duration before restore
(Must be 10 seconds in a UL installation)
.................................................
seconds
....
0247
......
005
_______
Smoke verification smoke power restore settling delay durantion
(Must be 25 seconds in a UL installation)
................................................
seconds
....
0248
......
010
_______
Smoke verification "window" delay duration
(Must be 120 seconds in a UL installation)
..............................................
seconds
....
0249
......
120
_______
Answer service callback override wait time
....................................................
seconds
....
0470
......
025
_______
Number of rings for pickup (minimum of 002, 000 disables )
..........................
rings
.........
0458
......
010
_______
Inactivity time before automatic hang up while in user phone access
............
seconds
....
0556
......
015
_______
Inactivity time before automatic hang up/exit when programming
.................
seconds
....
0557
......
060
_______
Delay before dialing after activation Phone #1 (000 - disables)
......................
seconds
....
0437
......
002
_______
Delay before dialing after activation Phone #2 (000 - disables)
......................
seconds
....
0438
......
002
_______
Off-hook time during listen-in before automatic hang-up (000 - 256 seconds) seconds
....
0453
......
120
_______
Central Station handshake wait period
.............................................................
seconds
....
0455
......
025
_______
Two-way callback from central station wait period
..........................................
minutes
....
0461
......
002
_______
Voice only and two-way callback wait period for a valid code
.......................
seconds
....
0465
......
060
_______
Maximum number of dialing attempts Phone #1
..............................................
attempts
...
0449
......
008
_______
Maximum number of dialing attempts Phone #2
..............................................
attempts
...
0450
......
008
_______
Touch tone (000) or pulse (001) dialing
...............................................................................
0454
......
000
_______
Ignore dial tone (for use with cellular backup) (001 - enabled)
.........................................
0466
......
000
_______
Number of disappearing code activations
........................................................
activation
.
0073
......
001
_______
Auto event upload dial attempts
........................................................................
attempts
...
0185
......
008
_______
# Swinger activations before Auto-Bypass
........................................................
activation
.
0115
......
000
_______
# Swinger time frame activations occur within
................................................
hours
........
0116
......
024
_______
Time extended monitor is displayed on the keypad (000 - continuous)
...........
seconds
....
0175
......
030
_______
Time between speech/beeps when extended monitor is active (000 - disable) seconds
....
0176
......
005
_______
* 000 disables (Must be enabled for UL installation)
# Not permitted in a UL installation
User Code Options
Options : Enter total - A description of each option is available in the Glossary Location Value
Duress
...........................................................................................................................................
001
Disappearing
.................................................................................................................................
004
Enable master functions - bypass mode, extended monitor, user code changes
........................
008
Works on remote telephone
.........................................................................................................
016
Works on keypads
........................................................................................................................
032
Works on local telephones
...........................................................................................................
064
Generate open report to CS and/or Event Memory log
................................................................
002
Generate close report to CS and/or Event Memory log
...............................................................
128
Default - User code 1 (all others default 000)
...........................................................
0065
.......
250
Program Mode Access Code Options
..........................................................................
0549
.......
048
Vista de pagina 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 63 64

Comentarios a estos manuales