Sequence of Operation
System Sequence of Events
Objective Equipment List
When motion is detected during a specific time of day period the system will turn on a light
and turn it off after a programmed countdown time. If motion is detected again within the
timed turn-off period then the light will remain on and the countdown will restart.
1) When motion is detected Zone 1 will be activated and the system will speak Motion
Detected.
2) Auxiliary Output pin 1(control channel 34) is linked to Zone 1 and will provide a ground
signal to the normally open contact of the on-board relay (Auxiliary Output 8, Control
Channel 33) whenever Zone 1 is activated.
3) The on-board relay will energize every day during a specified time period and this will
allow the ground signal from Auxiliary Output pin 1 to activate Zone 2.
4) The X-10 light (Control Channel 35) is linked to Zone 2 and will turn on whenever Zone 2
is activated and remain on until the programmed countdown time is over. If Zone 2 is
activated again within the countdown time the light will remain on and the countdown will
restart.
¨ Apex Destiny 6100 control panel, rev. 8.05 or greater
¨ Hardwire Motion Detector
¨ X-10 PRO Power Line Interface Module, PSC05
¨ X-10 PRO Incandescent Wall Switch Module, PLW01
- Motion Activated Light During Specified Time -
Provide lighting
when motion is
detected during
a specified time
period.
Apex Technical Support 800-272-7937
Option 1
X-10 PRO Technical Support 800-832-4003
Page 2-9
- Application Note -
Home Control