Sequence of Operation
System Sequence of Events
Objective Equipment List
¨ Apex Destiny 6100 control panel,
rev. 8.05 or greater
¨ Apex Relay Expansion Module, EXP8
¨ Apex Temperature Sensor, TS16
¨ W.W. Grainger, ICM203 Delay-On-Break Relay,
p/n 4E234
¨ Existing Mechanical Thermostat
- HVAC Temperature Control - Mechanical Thermostat -
Energy Savings While in the Away Mode
Provide energy savings in the
Away mode by maintaining
the temperature at a lower
heating setpoint and a higher
cooling setpoint.
When armed to Away the system will interrupt control power to the existing mechanical
thermostat and turn the HVAC system off. Control power is restored to the thermostat when the
temperature drops to the TS16 low limit setpoint or rises to the high limit setpoint allowing the
HVAC system to turn on and bring the temperature back to within the low and high limits. When
the system is disarmed control power will be restored to the thermostat and the temperature will
be maintained at its heating and cooling setpoints.
1) Arming the system to Away sends an ON command to Control Channel 1 energizing relay 1
on the EXP8 expansion board and interrupting control power to the thermostat.
2) When the temperature drops to the TS16 low limit setpoint or rises to the TS16 high limit
setpoint an ON command is sent to Control Channel 33 energizing relay 2 on the EXP8
expansion board and restoring control power to the thermostat.
3) When the temperature rises 2 degrees higher than the TS16 low limit setpoint or drops 2
degrees lower than the TS16 high limit setpoint an OFF command is sent to Control Chan-
nel 33 once again interrupting control power to the thermostat.
4) Disarming the system sends an OFF command to Control Channel 1 restoring power to the
thermostat which will maintain the temperature at its heating and cooling setpoints.
Note: Once control power has been interrupted to the thermostat, the delay-
on-break relay will prevent control power from being restored to the
thermostat again until the minimum off time of 4 minutes has elapsed.
This will help prevent short-cycling which could damage the HVAC unit.
Apex Technical Support 800-272-7937
Option 1
Page 3-3
- Application Note -
Energy Management